Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/10/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 04/08/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PANEL DIRECTORY TO BE REVISED SO IT IS CORRECT PIECE OF PAPER WEDGED IN PANEL NOT ACCEPTABLE 2. MISSING BACK PORCH LIGHT FIXTURE 3. AT CONDENSOR: a. FUSES NOT INSTALLED b. NEED LOCKNUTS FOR THINGS INTO UNIT c. EQUIPMENT GROUND TO BE GREEN ENTIRE LENGTH 4. PROVIDE DISCONNECTING MEANS FOR WATER HEATER, MIN. #10 GROUND PLANS SHOW NEW WATER HEATER 5. NO OPEN BULB TYPE FIXTURES ALLOWED IN CLOSET PARTIAL INSPECTION - GO THROUGH TO MAKE SURE PER PLAN/CODE |