Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
10/17/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
10/12/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. LABEL DISCONNECTS IN ATTIC AREA
2. PLEASE PROVIDE ILLUMINATION AT TRANSFORMER & DISCONNECT 110.26
3. HALL NIGHT LIGHT/EM LIGHT MISSING
10/09/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
CANCELLED BY MATT
10/08/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) SERVICE INSPECTION ONLY
10/05/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. REMOVE EQUIPMENT GROUNDING CONDUCTOR FROM CT CAN TO SERVICE DISCONNECT. THIS PROVIDES PARALLEL PATH FOR NEUTRAL CURRENTS. NEC 250.6
2. INSTALL FUSES AT SERVICE DISCONNECT
3. INSTALL PROPER SIZE LUG FOR GROUNDING CONDUCTOR AT 120/208V PANEL
4. CONNECT GROUNDING ELECTRODE CONDUTOR TO XO OF TRANSFORMER OR WHERE MAIN BONDING JUMPER IS TERMINATED. NEC 250.30(A)(2). IDENTIFY BONDING JUMPER
5. DO NOT USE TRANSFORMER FOR MOUNTING OF AC DISCONNECT
6. INSPECTOR TO VERIFY IF ELECTRICAL INSTALLATION & PLANS REQUIRES ENGINEER REVIEW & APPROVAL. THIS INSTALLATION HAS 277/480V 30 4W 100 AMP SERVICE TO PANEL. 60 AMP BREAKER IN 277/480V PANEL FEEDS 45KVA XFMR WHICH FEEDS 120/280V PANEL WITH 125A MAIN BREAKER.
10/01/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
RECALL WHEN READY