Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/07/2007 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 09/05/2007 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. WIRING NOT DONE TO SWITCH IN ELECTRIC CLOSET 2. SUPPORT FOR SIDE OF RECEPTACLE & SWITCH BOXES 3. MC CABLES TO BE SECURED WITHIN 12" OF BOXES 4. MISSING MUD RING ON EM/EXIT LIGHT 5. MC CABLES TO BE SUPPORTED/SECURED EVERY 6' 6. STRAP/SECURE EMT WITHIN 36" OF BOXES 7. MISSING EXIT AT REAR STAIRWAY 8. CANNOT USE BROWN/ORANGE/YELLOW FOR 120/208V CIRCUITS. 9. NEED TO USE BROWN/ORANGE/YELLOW COLORS FOR 277V CIRCUITS. 10. ENSURE MC CABLES ARE IN WALLS |