Permit: T07CM03252

Parcel: 14108521C

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
09/07/2007 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
09/05/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. WIRING NOT DONE TO SWITCH IN ELECTRIC CLOSET
2. SUPPORT FOR SIDE OF RECEPTACLE & SWITCH BOXES
3. MC CABLES TO BE SECURED WITHIN 12" OF BOXES
4. MISSING MUD RING ON EM/EXIT LIGHT
5. MC CABLES TO BE SUPPORTED/SECURED EVERY 6'
6. STRAP/SECURE EMT WITHIN 36" OF BOXES
7. MISSING EXIT AT REAR STAIRWAY
8. CANNOT USE BROWN/ORANGE/YELLOW FOR 120/208V CIRCUITS.
9. NEED TO USE BROWN/ORANGE/YELLOW COLORS FOR 277V CIRCUITS.
10. ENSURE MC CABLES ARE IN WALLS