Permit: T07CM03249

Parcel: 12709011M

Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Permit Number - T07CM03249

Inspection Description - MECHANICAL - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
02/27/2008 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
CORRECTIONS HAVE BEEN MADE
OK FOR CEILING TILES
02/22/2008 MECHANICAL - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
- PROVIDE LINED BOOTS ON ALL RETURN AIR GRILLES
AS PER PLAN & SUPPORT TO STRUCTURE
- SUPPORT FLEX DUCT UP OFF OF GRID & SECURE DIFFUSERS THAT HAVE BEEN RELOCATED
- RETURN MISSING IN CAFE. SUPPLY MISSING IN ROOM 27
- ON FINAL PROVIDE AIR BALANCE REPORT
- REPAIR HOLES IN FIREWALL