Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/27/2008 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* CORRECTIONS HAVE BEEN MADE OK FOR CEILING TILES |
|
| 02/22/2008 | MECHANICAL - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* - PROVIDE LINED BOOTS ON ALL RETURN AIR GRILLES AS PER PLAN & SUPPORT TO STRUCTURE - SUPPORT FLEX DUCT UP OFF OF GRID & SECURE DIFFUSERS THAT HAVE BEEN RELOCATED - RETURN MISSING IN CAFE. SUPPLY MISSING IN ROOM 27 - ON FINAL PROVIDE AIR BALANCE REPORT - REPAIR HOLES IN FIREWALL |