Permit: T07CM03249

Parcel: 12709011M

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T07CM03249

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
04/30/2008 PLUMBING - FINAL Approved IVRS - Inspection :*
04/14/2008 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. DW HOSE SHALL BE SECURED WITHIN 2" OF SINK FLOOD LEVEL OR INSTALL AIR GAP FITTING PER UPC REQUIREMENTS
2. R O WATER EQUIPMENT SHALL HAVE AN AIR GAP FITTING
3. COFFEE MACHINE REQUIRES A BACKFLOW DEVICE ON WATER SUPPLY
02/29/2008 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
PROVIDE CORRECT INSTALL OF DISHWASHER
02/28/2008 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
CLIPS MISSING ON SINK
CO MISSING
P-TRAP BACKWARDS
DISHWASHER NOT INSTALLED