Inspection History: ELECTRIC - PROGRESS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/03/2008 | ELECTRIC - PROGRESS | Approved | ||
| 05/08/2008 | ELECTRIC - PROGRESS | Not ready for Inspection | IVRS - Inspection :* | |
| 05/02/2008 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* 1. ADDRESS METERS AND DISCONNECTS WITH PERMANENT ADDRESS LABELS 2. COMPLETE WIRING FOR SERVICE 3. INSTALL ISOLATED GROUND IN PANEL PER PLAN (A) |
|
| 04/25/2008 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* - POST BOND FOR TEMP POWER FOR TEST - COMPLETE SERVICE & GROUNDING |
|
| 04/04/2008 | ELECTRIC - PROGRESS | Not ready for Inspection | IVRS - Inspection :* 1. VERIFY USAGE OF ENT IN WALLS 2. PROTECT ENT AT BASE PLATE 3. FIRE ALARM BOXES TO BE RED 760 4. FINISH SUPPORTING EMT WITHIN 3' OF BOXES |
|
| 03/10/2008 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* - OK GROUNDING AT GEN. PAD - WHEN USING STEEL RACEWAY FOR GROUNDING ELECTRODE ENCLOSURE, A1 BOND BUSHING IS REQUIRED 250 NEC |
|
| 03/07/2008 | ELECTRIC - PROGRESS | Denied | IVRS - Inspection : There is no access to the site.| 920* LOCKED NO ACCESS 2:20 PM |