Permit: T07CM03241

Parcel: 13727099B


Addresses:

1430 W VALENCIA RD

Inspection Status: Approved

Inspection History: ELECTRIC - PROGRESS

Date Description Inspector Results Comments
06/03/2008 ELECTRIC - PROGRESS Approved
05/08/2008 ELECTRIC - PROGRESS Not ready for Inspection IVRS - Inspection :*
05/02/2008 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
1. ADDRESS METERS AND DISCONNECTS WITH PERMANENT ADDRESS LABELS
2. COMPLETE WIRING FOR SERVICE
3. INSTALL ISOLATED GROUND IN PANEL PER PLAN (A)
04/25/2008 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
- POST BOND FOR TEMP POWER FOR TEST
- COMPLETE SERVICE & GROUNDING
04/04/2008 ELECTRIC - PROGRESS Not ready for Inspection IVRS - Inspection :*
1. VERIFY USAGE OF ENT IN WALLS
2. PROTECT ENT AT BASE PLATE
3. FIRE ALARM BOXES TO BE RED 760
4. FINISH SUPPORTING EMT WITHIN 3' OF BOXES
03/10/2008 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
- OK GROUNDING AT GEN. PAD
- WHEN USING STEEL RACEWAY FOR GROUNDING ELECTRODE ENCLOSURE, A1 BOND BUSHING IS REQUIRED 250 NEC
03/07/2008 ELECTRIC - PROGRESS Denied IVRS - Inspection :
There is no access to the site.| 920*
LOCKED NO ACCESS 2:20 PM