Permit: T07CM03241

Parcel: 13727099B


Addresses:

1430 W VALENCIA RD

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
06/03/2008 ELECTRIC - INTERMEDIATE Approved
05/07/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
CONTR. REQUEST AFTER HRS. INSP. PAID $150.00 CK#3533

1. CANNOT INSTALL (4) 500MCM TAWN IN 2 1/2" CONDUIT PER TABLES C-8 NEC
2. PROVIDE INFO. FOR CONDUCTOR SIZE, QUANTITY & MATERIAL ON REVISED DRAWING, FOR SERVICE MODIFICATIONS.
04/08/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
PANELS ARE SURFACE MTD. OK WALLS
04/07/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
SEE NOTES FOR ENT USE LAST INSP.
10/30/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK FEEDERS FOR TRANSER & EM. POWER BELOW SLAB, SUBJECT TO APPROVED PLANS.
10/16/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK UNDER SLAB CONDUITS