Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/03/2008 | ELECTRIC - INTERMEDIATE | Approved | ||
| 05/07/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* CONTR. REQUEST AFTER HRS. INSP. PAID $150.00 CK#3533 1. CANNOT INSTALL (4) 500MCM TAWN IN 2 1/2" CONDUIT PER TABLES C-8 NEC 2. PROVIDE INFO. FOR CONDUCTOR SIZE, QUANTITY & MATERIAL ON REVISED DRAWING, FOR SERVICE MODIFICATIONS. |
|
| 04/08/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* PANELS ARE SURFACE MTD. OK WALLS |
|
| 04/07/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* SEE NOTES FOR ENT USE LAST INSP. |
|
| 10/30/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK FEEDERS FOR TRANSER & EM. POWER BELOW SLAB, SUBJECT TO APPROVED PLANS. |
|
| 10/16/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK UNDER SLAB CONDUITS |