Permit: T07CM03232

Parcel: 140553300

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
10/04/2007 FRAMING Approved IVRS - Inspection :*
1) 190 HOUSE 390 PLAN ON SITE
2) DBL #2 SHEARWALL NOT CONNECTED TO TRUSS SYSTEM PER APPROVED PLAN
10/01/2007 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NO PLANS ON SITE
2) ITEM 2, 4 & 5 FROM 9/28/07 NOT DONE
09/28/2007 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) SHEARWALL 9 REQUIRES 3/4" ANCHOR BOLTS AT 24" ON CENTER
2) SHEARWALL 2 AT DEN REQUIRES CONNECTION TO FLOOR TRUSS PER 14 S1.1
3) HOLDOWNS MUST BE INSTALLED VERTICALLY OR PROVIDE SIMPSON APPROVAL
4) TWO HOLDOWNS ON SOUTH WALL NOT INSTALLED AT ENDS OF SHEARWALLS
5) WEST WALL HOLDOWNS NOT IN PROPER LOCATION
09/25/2007 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) MISSING 3/4" DIAMETER BOLTS STAIR BOTTOM PLATE 24" ON CENTER
2) SHEAR TRANSFER DEN N/S WALL
3) H.D.'S ON SOUTH WALL LIVING ROOM NOT PLUMB, MISSING NUTS
4) MSTR TOILET NOT VENTED CORRECTLY
5) ALL H.D.'S MISSING NUTS
6) KIT CEILING PEX TO CLOSE TO CANS
7) NEED VERTICAL BACKING SHOWER MSTR
8) REAR HANGERS (HIP) FILL HOLES