Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/21/2007 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
| 11/19/2007 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) CHANGE A/C BREAKER TO 30 AMPS OR INSTALL FUSED DISCONNECT 2) CHANGE AIR HANDLER BREAKER TO 30 AMPS OR INSTALL FUSED DISCONNECT |
|
| 11/13/2007 | BUILDING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1 POWER SHUT OFF BY TEP BY MISTAKE, CANNOT POWER CHECK |