Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T07CM03222
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/02/2007 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
09/28/2007 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* PLEASE HAVE ELECTRICIAN ON SITE FOR FINAL TO ACCESS EQUIPMENT AND ANSWER QUESTION |
|
09/25/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK WALL ROOM 106 OK TILES 2ND FLOOR 1. WHERE DOWN WALL DOES M/C GO TO? |
|
09/19/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | 1) SUPPORT M/C CABLE UPON WALL EXITING 2) BOX OVER FILLED 312.16 3) TIGHTEN LOOSE FITTING 4) OPEN CEILING TO INSPECT M/C RUN 5) M/C NOT TO BE SUPPORTED OFF OF CONDUIT 6) WHAT WORK IS BEING DONE IN SUITE #140 7) FRAMIN IN SUITE #200, ROOM #104-OK TO SHEETROCK |