Permit: T07CM03220

Parcel: 141340590

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T07CM03220

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
01/04/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
10/24/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PROVIDE LADDER FOR ROOF ACCESS
2. INVERTOR NOT PER APPROVED PLANS
3. NON-METALLIC BOXES TO BE USED ONLY WITH NON-METALLIC WIRING METHODS - NEC 314.3
4. WALL BLOCKING ACCESS INTO LB - NEC 314.29
5. RACEWAYS TO BE MECHANICALLY SECURED TO BOXES. NEED FITTINGS AT ALL RACEWAY CONNECTIONS - NEC 300.10
6. FUSES ARE NOT A DISCONNECTING MEANS. PROVIDE DISCONNECTING MEANS FOR FUSES OPERATING OVER 150V
NEC 240.40
7. LABELING NOT PER APPROVED PLANS
8. NOT A COMPLETE INSPECTION
9. PLEASE HAVE METER REMOVED FOR NEXT INSPECTION
10. RECALL WHEN READY