Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T07CM03220
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/04/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
10/24/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PROVIDE LADDER FOR ROOF ACCESS 2. INVERTOR NOT PER APPROVED PLANS 3. NON-METALLIC BOXES TO BE USED ONLY WITH NON-METALLIC WIRING METHODS - NEC 314.3 4. WALL BLOCKING ACCESS INTO LB - NEC 314.29 5. RACEWAYS TO BE MECHANICALLY SECURED TO BOXES. NEED FITTINGS AT ALL RACEWAY CONNECTIONS - NEC 300.10 6. FUSES ARE NOT A DISCONNECTING MEANS. PROVIDE DISCONNECTING MEANS FOR FUSES OPERATING OVER 150V NEC 240.40 7. LABELING NOT PER APPROVED PLANS 8. NOT A COMPLETE INSPECTION 9. PLEASE HAVE METER REMOVED FOR NEXT INSPECTION 10. RECALL WHEN READY |