Permit: T07CM03206

Parcel: 117131560


Addresses:

192 S STONE AV


Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Permit Number - T07CM03206

Inspection Description - MECHANICAL - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
05/28/2009 MECHANICAL - INTERMEDIATE Approved IVRS - Inspection :*
02/05/2009 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK TO SHEETROCK RESTROOMS
AND CORRIDOR MECHANICAL ONLY
01/15/2009 MECHANICAL - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
01/14/2009 MECHANICAL - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. FLEX DUCT NOT TO EXCEED 8' PER PLANS
2. PROVIDE CONICAL OR BOOT TAPS PER PLANS
3. FLEX DUCT NOT INSTALLED AND CONNECTED PER PLANS
4. PROVIDE SHEETMETAL STRAPS PER PLANS (NO NYLON)
5. PROVIDE MINIMUM 1.5 RADIUS BENDS ON FLEX DUCT
6. PROVIDE BALANCING DAMPERS AT BRANCH TAKE-OFF's
PER PLANS
7. PROVIDE APPROVED HANGERS FOR REFRIG. LINES
(NO PANDUIT)
8. SEAL ALL DUCT WITH SEALER INCLUDING END CAPS AND PLENUM DROPS PER PLANS (NO TAPE ALLOWED)
9. PROVIDE APPROVED WIRING TO CONDENSING UNITS
PER N.E.C.C. (CORD NOT ALLOWED)
10. INSTALL BACK DRAFT DAMPER IN EXHAUST FAN
11. PROVIDE GUARD RAILS PER IMC 304.10 ON ALL SERVICABLE EQUIPMENT WITHIN 10' OF ROOF EDGE
12. ALL CONDENSATE PIPING TO BE TYPE "M" PER PLANS