Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/28/2009 | MECHANICAL - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 02/05/2009 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK TO SHEETROCK RESTROOMS AND CORRIDOR MECHANICAL ONLY |
|
| 01/15/2009 | MECHANICAL - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
| 01/14/2009 | MECHANICAL - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. FLEX DUCT NOT TO EXCEED 8' PER PLANS 2. PROVIDE CONICAL OR BOOT TAPS PER PLANS 3. FLEX DUCT NOT INSTALLED AND CONNECTED PER PLANS 4. PROVIDE SHEETMETAL STRAPS PER PLANS (NO NYLON) 5. PROVIDE MINIMUM 1.5 RADIUS BENDS ON FLEX DUCT 6. PROVIDE BALANCING DAMPERS AT BRANCH TAKE-OFF's PER PLANS 7. PROVIDE APPROVED HANGERS FOR REFRIG. LINES (NO PANDUIT) 8. SEAL ALL DUCT WITH SEALER INCLUDING END CAPS AND PLENUM DROPS PER PLANS (NO TAPE ALLOWED) 9. PROVIDE APPROVED WIRING TO CONDENSING UNITS PER N.E.C.C. (CORD NOT ALLOWED) 10. INSTALL BACK DRAFT DAMPER IN EXHAUST FAN 11. PROVIDE GUARD RAILS PER IMC 304.10 ON ALL SERVICABLE EQUIPMENT WITHIN 10' OF ROOF EDGE 12. ALL CONDENSATE PIPING TO BE TYPE "M" PER PLANS |