Date Description Inspector Results Comments
07/01/2009 ELECTRIC - FINAL Approved IVRS - Inspection :*
1) OK ELECTRIC
06/22/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
05/28/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
STAGE & OUTSIDE:
1. CONTACTORS TO BE LISTED
2. PANEL SCHEDULE TO BE AS PER 408.4
3. PLEASE PROVIDE ACCESS TO STAGE LIGHTS
4. PLANS NOT REFLECTIVE OF WORK INSTALLED

BUILDING:
1. LABEL AC SWITCHES
2. FINISH LIGHTING
3. EXISTING PANEL COVER CANNOT OPEN
4. PLANS NOT REFLECTIVE OF WORK INSTALLED
05/26/2009 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
FINISH ELECTRICAL WORK - PLEASE HAVE BOTH ELECTRICAL CONTRACTORS ON SITE TO ANSWER QUESTIONS