Permit: T07CM03191

Parcel: 140252450

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
01/08/2008 FRAMING Approved IVRS - Inspection :*
01/07/2008 FRAMING Denied NOT READY
01/04/2008 FRAMING Partial Approval IVRS - Inspection :*
12/28/2007 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
GATE LOCKED 9:03 AM

ON THE 17TH - I CAME BACK 3 TIMES BECAUSE THIS GATE WASN'T OPEN. IF YOU NEED TO LEAVE A MESSAGE FOR THE INSPECTOR TO CONTACT YOU, PLEASE DO SO. THANK YOU.
12/17/2007 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) THIS HOUSE NOT READY FOR INSPECTION: STUCCO CAULK ALL PENETRATIONS PATCH AT FRONT COLUMN
2) RISER AT SERVICE NOT PLUMB NOT SECURED, OR WRAP AND NO ADDRESS
3) MECH IS INCOMPLETE BEING INSTALLED NOW SECURE CONDENSATE LINE AT EXT.
4) NEED TUB BACKING
5) NAIL PROTECTION WIRE AND PIPES MISSING THRU OUT
6) STAPLES MISSING ROMEX WEST BATH
7) NO DWV TEST, NO POTABLE H20 PRESSURE
8) PLAN CALLS FOR #12 CU AIR HANDLER VERIFY IF THERE IS A HEAT STRIP
9) STUDS MISSING IN CLOSET WALL NEXT FURNACE
10) ROMEX OUTSIDE WALL AT MASTER TUB
11) STOPPED INSPECTION
12/12/2007 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) COMPLETE ENTRY AND MAIN SERVICE
2) SEAL PENETRATIONS
3) REINFORCE WINDOWS AND DOORS
4) BROKEN WINDOWS
5) INSTALL ADDRESS RAISED METAL LETTERS
6) WRAP RISER