Permit: T07CM03179

Parcel: 12604011A


Addresses:

4458 E SPEEDWAY BL


Inspection Status: Partial Approval

Inspection History: ELECTRIC - FINAL

Permit Number - T07CM03179

Inspection Description - ELECTRIC - FINAL

Inspection Status - Partial Approval

Date Description Inspector Results Comments
08/02/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) FINISH OUTSIDE CONNECTIONS
08/01/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. PREVENT OBJECTIONABLE CURRENT 250.6
WE HAVE A PARALLEL PATH OF GROUND
2. MAINTAIN WIRE BENDING RADIUS
3. USE APPROVED CONNECTORS LISTED FOR NUMBER OF CABLES
4. BOND JUNCTION BOX ENCLOSURE
5. SECURE CABLE WITHIN 8" OF PASS THRU NIPPLE
6. VDV SPLICES TO BE ACCESSIBLE
7. FINISH OUTSIDE CONNECTIONS
8. LABEL PANEL AS PER 408.4 -- NO ABBREVIATIONS