Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/26/2007 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* MIGUEL I FOUND IT!! CONNECTION UNDER LAV -- OK TO COVER |
|
| 10/17/2007 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1. CLOSET FLANGES TO BE SCREWED TO THE FLOOR 2. ALL OVERHEAD COPPER TO BE SUPPORTED SO AS TO PREVENT "BANGING" 3. "EXISTING" WATER HEATER IS NOT 75 GALLON HEATER IT IS A "BOOTLEGGED" 30 GALLON GAS FIRED HEATER. IT HAS NO EXPANSION, NO VACUUM RELIEF VALVE, NO T&P RELIEF DRAIN, AND DOES NOT MEET THE REQUIREMENTS OF 2003 IECC 4. COPPER PASSING THROUGH MASONRY WALL TO BE PROTECTED. 5. CONTINUED "NOT READY" WILL RESULT IN A REINSPECTION FEE |
|
| 10/15/2007 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 702 POSTED ON DOOR 706 FOR ACCESS DWV NOT UNDER TEST PROVIDE INSP. HISTORY PERM CAP 2" ABS IN DOORWAY FLOOR VENTING NOT PER PLAN - REDLINE ALL CHANGES CONDUIT TOUCHING COPPER PIPING NOT SUPPORTED NEAR DUCT NEED BACKING AT MS FAUCET |