Permit: T07CM03166

Parcel: 12514006A

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
10/26/2007 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
MIGUEL I FOUND IT!!
CONNECTION UNDER LAV -- OK TO COVER
10/17/2007 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1. CLOSET FLANGES TO BE SCREWED TO THE FLOOR
2. ALL OVERHEAD COPPER TO BE SUPPORTED SO AS TO PREVENT "BANGING"
3. "EXISTING" WATER HEATER IS NOT 75 GALLON HEATER
IT IS A "BOOTLEGGED" 30 GALLON GAS FIRED HEATER. IT HAS NO EXPANSION, NO VACUUM RELIEF VALVE, NO T&P
RELIEF DRAIN, AND DOES NOT MEET THE REQUIREMENTS
OF 2003 IECC
4. COPPER PASSING THROUGH MASONRY WALL TO BE PROTECTED.
5. CONTINUED "NOT READY" WILL RESULT IN A
REINSPECTION FEE
10/15/2007 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
702 POSTED ON DOOR 706 FOR ACCESS
DWV NOT UNDER TEST PROVIDE INSP. HISTORY
PERM CAP 2" ABS IN DOORWAY FLOOR
VENTING NOT PER PLAN - REDLINE ALL CHANGES
CONDUIT TOUCHING COPPER
PIPING NOT SUPPORTED NEAR DUCT
NEED BACKING AT MS FAUCET