Permit: T07CM03166

Parcel: 12514006A

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
12/06/2007 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
10/22/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK BATH AREA WALL/CEILING COVER
10/17/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
CORRECTIONS HAVE NOT BEEN COMPLETED, DO NOT CALL BEFORE ALL PREVIOUS CORRECTIONS ARE COMPLETED OR A FEE MAY BE CHARGED
10/15/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. CHANGE PERMIT TO CORRECT SUITE #
2. INSTALL EX. FANS & MUD RINGS
3. INSTALL NAIL PLATES AS NEEDED WHERE HOLE IS 1 1/4 OR LESS FROM STUD FACE
4. GROUND TO WRAP MINIMUM 2/3 AROUND SCREWS AND TIGHTEN
5. IDENTIFY WHITE USED AT HOT IN SWITCH LEGS
6. WIRING NOT PER PLAN
7. HAVE MC BELOW CEILING
8. NEED NAIL PLATES FOR NOTCHED OPENINGS
9. SECURE MC WITHING 12" OF TERMINATIONS
10. DEMO ALL UNUSED EQUIPMENT

DO NOT DRYWALL