Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/06/2007 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 10/22/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK BATH AREA WALL/CEILING COVER |
|
| 10/17/2007 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* CORRECTIONS HAVE NOT BEEN COMPLETED, DO NOT CALL BEFORE ALL PREVIOUS CORRECTIONS ARE COMPLETED OR A FEE MAY BE CHARGED |
|
| 10/15/2007 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. CHANGE PERMIT TO CORRECT SUITE # 2. INSTALL EX. FANS & MUD RINGS 3. INSTALL NAIL PLATES AS NEEDED WHERE HOLE IS 1 1/4 OR LESS FROM STUD FACE 4. GROUND TO WRAP MINIMUM 2/3 AROUND SCREWS AND TIGHTEN 5. IDENTIFY WHITE USED AT HOT IN SWITCH LEGS 6. WIRING NOT PER PLAN 7. HAVE MC BELOW CEILING 8. NEED NAIL PLATES FOR NOTCHED OPENINGS 9. SECURE MC WITHING 12" OF TERMINATIONS 10. DEMO ALL UNUSED EQUIPMENT DO NOT DRYWALL |