Permit: T07CM03161

Parcel: 12702357A


Addresses:

635 N CRAYCROFT RD

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
01/23/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
01/22/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
FINISH #2, 3 FROM 1/18/08 INSP.
FINISH #3, 4 FROM 1/15/08 INSP.
FINISH #1 FROM 1/14/08 INSP.
FINISH #4 FROM 1/4/08 INSP.
01/18/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. CIRCUIT DIRECTORIES TO BE AS PER 408.4
2. BOXES MORE THAN 1/4" FROM BOX TO SURFACE 314.20
3. MOTION SENSORS TO BE FOR USE WITH FLUORESCENT LIGHTS
4. USE APPROVED GRID WIRE FOR LIGHT
5. SUPPORT BOXES TO GRID - TILE IS NOT FOR SUPPORT
6. CANNOT TRIM CONDUCTORS
7. FINISH PREVIOUS ITEMS 2,3, 4, 5 - 1/15/08
1 - 1/14/08
4 - 1/4/08

DO NOT OCCUPY

*RECEIVED LETTER FOR SWITCHING
01/17/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. MEET WITH NEW ELECTRICIAN TO EXPLAIN JOB
01/15/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
ROOF:
1. MAINTAIN WORKING CLEARANCES
2. SUPPORT CONDUIT AS PER CODE
3. BOND ENCLOSURES
4. LABEL DISCONNECTS
5. SUPPORT STANDS TO ROOF
6. MAINTENANCE RECEPTACLE TO BE WITHIN 25' OF EQUIPMENT
7. EXPOSED CONDUCTORS IN EXHAUST FANS
8. DERATE CONDUCTORS PER 310.15

2ND FLOOR:
1. MAINTAIN WORKING CLEARANCES INSTA-HOT DISCONNECT
2. SUPPORT CONDUIT ABOVE PANEL
3. FIXTURE NOT WORKING
4. WHO ADDED NEW FIXTURES & DEVICES TO BATHROOM
DEVICES NOT GFCI PROTECTED ALSO, OPEN GROUND.
01/14/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. USE APPROVED MOTION SENSOR FOR CEILING -
NOT WALL SWITCH
2. EXIT LIGHTS NOT WORKING
3. FINISH PREVIOUS ITEMS
01/11/2008 ELECTRIC - FINAL Cancelled IVRS - RI canceled
01/04/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. SUPPORT CONDUITS AS PER CODE - 358.30
2. BOXES MORE THAN 1/8" AROUND BOXES - 314.21
3. CORRECTLY IDENTIFY UNGROUNDED CONDUCTORS - 200.7
4. GROUND JUNCTION BOXES PER 250.148
5. STORAGE ROOM 103 MISSING SWITCH AND MOTION SENSOR
6. SWITCHING IS NOT TANDEM AS PER PLANS
7. IF PANEL CLEANED A 3RD PARTY REPORT INCLUDING DIELECTRIC TESTING WILL BE NEEDED