Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/23/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 01/22/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* FINISH #2, 3 FROM 1/18/08 INSP. FINISH #3, 4 FROM 1/15/08 INSP. FINISH #1 FROM 1/14/08 INSP. FINISH #4 FROM 1/4/08 INSP. |
|
| 01/18/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. CIRCUIT DIRECTORIES TO BE AS PER 408.4 2. BOXES MORE THAN 1/4" FROM BOX TO SURFACE 314.20 3. MOTION SENSORS TO BE FOR USE WITH FLUORESCENT LIGHTS 4. USE APPROVED GRID WIRE FOR LIGHT 5. SUPPORT BOXES TO GRID - TILE IS NOT FOR SUPPORT 6. CANNOT TRIM CONDUCTORS 7. FINISH PREVIOUS ITEMS 2,3, 4, 5 - 1/15/08 1 - 1/14/08 4 - 1/4/08 DO NOT OCCUPY *RECEIVED LETTER FOR SWITCHING |
|
| 01/17/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. MEET WITH NEW ELECTRICIAN TO EXPLAIN JOB |
|
| 01/15/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* ROOF: 1. MAINTAIN WORKING CLEARANCES 2. SUPPORT CONDUIT AS PER CODE 3. BOND ENCLOSURES 4. LABEL DISCONNECTS 5. SUPPORT STANDS TO ROOF 6. MAINTENANCE RECEPTACLE TO BE WITHIN 25' OF EQUIPMENT 7. EXPOSED CONDUCTORS IN EXHAUST FANS 8. DERATE CONDUCTORS PER 310.15 2ND FLOOR: 1. MAINTAIN WORKING CLEARANCES INSTA-HOT DISCONNECT 2. SUPPORT CONDUIT ABOVE PANEL 3. FIXTURE NOT WORKING 4. WHO ADDED NEW FIXTURES & DEVICES TO BATHROOM DEVICES NOT GFCI PROTECTED ALSO, OPEN GROUND. |
|
| 01/14/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. USE APPROVED MOTION SENSOR FOR CEILING - NOT WALL SWITCH 2. EXIT LIGHTS NOT WORKING 3. FINISH PREVIOUS ITEMS |
|
| 01/11/2008 | ELECTRIC - FINAL | Cancelled | IVRS - RI canceled | |
| 01/04/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. SUPPORT CONDUITS AS PER CODE - 358.30 2. BOXES MORE THAN 1/8" AROUND BOXES - 314.21 3. CORRECTLY IDENTIFY UNGROUNDED CONDUCTORS - 200.7 4. GROUND JUNCTION BOXES PER 250.148 5. STORAGE ROOM 103 MISSING SWITCH AND MOTION SENSOR 6. SWITCHING IS NOT TANDEM AS PER PLANS 7. IF PANEL CLEANED A 3RD PARTY REPORT INCLUDING DIELECTRIC TESTING WILL BE NEEDED |