Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/23/2008 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 11/20/2007 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 11/13/2007 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) SUPPORT WIRES NEEDED FOR FIXTURES 2) ATTACH FIXTURES TO GRID 410.16 3) PROTECT M/C CABLE AT TOP PLATE 4) FINISH PREVIOUS ITEMS UPSTAIRS |
|
| 10/25/2007 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1. NO MORE THAN 360 DEG. IN CONDUIT RUNS 2. FINISH VDV CABLING 3. FINISH ROOMS 116, 111, 214 |
|
| 10/22/2007 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. STRAP MC CABLE WITHIN 12" OF JUNCTION BOXES 2. SECURE LIGHT FIXTURE TO CEILING GRID. USE ALL 4 CLIPS ON LIGHT FIXTURE OR SCREW TO GRID 3. CLOSE ALL OPEN JUNCTION BOXES 4. INSTALL K.O SEALS IN JUNCTION BOXES WERE MISSING 5. CHECK ALL LIGHT FIXTURES HAVE TIE WIRES 6. REMOVE CUT/OLD WIRING FROM JUNCTION BOXES AND INSTALL K.O SEALS |