Permit: T07CM03161

Parcel: 12702357A


Addresses:

635 N CRAYCROFT RD

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Date Description Inspector Results Comments
01/23/2008 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
11/20/2007 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
11/13/2007 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) SUPPORT WIRES NEEDED FOR FIXTURES
2) ATTACH FIXTURES TO GRID 410.16
3) PROTECT M/C CABLE AT TOP PLATE
4) FINISH PREVIOUS ITEMS UPSTAIRS
10/25/2007 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1. NO MORE THAN 360 DEG. IN CONDUIT RUNS
2. FINISH VDV CABLING
3. FINISH ROOMS 116, 111, 214
10/22/2007 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. STRAP MC CABLE WITHIN 12" OF JUNCTION BOXES
2. SECURE LIGHT FIXTURE TO CEILING GRID. USE ALL 4 CLIPS ON LIGHT FIXTURE OR SCREW TO GRID
3. CLOSE ALL OPEN JUNCTION BOXES
4. INSTALL K.O SEALS IN JUNCTION BOXES WERE MISSING
5. CHECK ALL LIGHT FIXTURES HAVE TIE WIRES
6. REMOVE CUT/OLD WIRING FROM JUNCTION BOXES AND INSTALL K.O SEALS