Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/09/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 12/18/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PANEL DIRECTORIES TO BE COMPLETE AND CORRECT ALSO, SECURE DIRECTORIES SO THEY DO NOT FALL OUT ALL CKT'S IDENTIFIED AND GOING TO WHAT DIRECTORIES SAY THEY ARE GOING TO. |
|
| 12/10/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. WIRING NOT PER PLAN - REVISE AS NEEDED TO SHOW ACTUAL INSTALLATION 2. PROVIDE PANEL DIRECTORY (NOT SHARPIE) AND CORRECTLY IDENTIFY CKT'S 3. SELF TAP SCREW NOT ALLOWED FOR GROUND LUG - REMOVE PAINT UNDER LUGS ALSO 4. CONTACTOR J-BOX NOT GROUNDED 5. GROUND #6 & SMALLER TO BE GREEN, NEUTRAL #6 AND SMALLER TO BE WHITE (NOT TAPE) 6. TIGHTEN ALL CLAMPS/STRAPS AND FITTINGS |
|
| 11/26/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* MUST PROVIDE APPROVED PLANS SHOWING ALL ELECTRICAL WORK ASSOCIATED WITH HOOD INSTALLATION, I.E MAKE UP AIR INTERLOCK, ETC. |
|
| 11/23/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. IT APPEARS NEW CONTROL SYSTEM INSTALLED FOR HOOD. PLEASE PROVIDE APPROVED ELECTRIC PLANS FOR ALL NEW WORK 2. PLEASE PROVIDE LADDER TO ACCESS ROOF |