Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T07CM03156
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/04/2007 | ELECTRIC - FINAL | Approved | ||
| 08/31/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* |
|
| 08/30/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* OK FOR CLEARANCE FOR TEMP POWER TMPP IS SUBJECT TO POSTING OF BOND |
|
| 08/29/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. BOXES MORE THAN 1/4" FROM BOX TO SURFACE NEED APPROVED EXTENDER RINGS 314.20 2. FINISH ELECTRIC 3. TERMINATE ALL CONDUCTORS AT PANEL AND FILL UNUSED OPENINGS 4. SEPARATE GROUNDS & NEUTRALS AT SUB-PANEL 5. PROVIDE REJECTION PINS AT SERVICE DISCONNECT AND FILL UNUSED OPENINGS 6. BREAKERS TO BE LISTED FOR USE BY MANUFACTURE |