Permit: T07CM03156

Parcel: 11451142A

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T07CM03156

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
09/04/2007 ELECTRIC - FINAL Approved
08/31/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
08/30/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK FOR CLEARANCE FOR TEMP POWER TMPP
IS SUBJECT TO POSTING OF BOND
08/29/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. BOXES MORE THAN 1/4" FROM BOX TO SURFACE NEED APPROVED EXTENDER RINGS 314.20
2. FINISH ELECTRIC
3. TERMINATE ALL CONDUCTORS AT PANEL AND FILL UNUSED OPENINGS
4. SEPARATE GROUNDS & NEUTRALS AT SUB-PANEL
5. PROVIDE REJECTION PINS AT SERVICE DISCONNECT AND FILL UNUSED OPENINGS
6. BREAKERS TO BE LISTED FOR USE BY MANUFACTURE