Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T07CM03151
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/11/2007 | FRAMING | Approved | IVRS - Inspection :* | |
12/10/2007 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) FIRESTOP ABOVE 3-GANG BOX TO LIVING ROOM AT FOYER CEILING HEIGHT 2) MINIMUM 30" CLEARANCE ABOVE ATTIC ACCESS 3) SEAL AROUND BOXES AND HOSE BIB SOUTH WALL 4) TURN BLOCK ON 4 GANG BOX UPSTAIRS BATHROOM WALL 5) PROTECT WIRES FROM GUSSETS IN GARAGE CEILING 6) SUPPORT 3" ABS MAXIMUM 48" IN GARAGE 7) MOUNT TPR LINE AT WATER HEATER FOR SOLAR |
|
12/07/2007 | FRAMING | Not ready for Inspection | IVRS - Inspection :* 1) CANCELLED PER JAMIE |