Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/19/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 05/07/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* KITCHEN INSPECTION ONLY 1. OK PARTIAL FINAL KITCHEN AND SERVICE AREA |
|
| 05/06/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. NUMEROUS VIOLATIONS ON ROOF TOO MANY TO LIST HAVE ELECTRICAL CONTRACTOR GO THROUGH ENTIRE ROOF AND MAKE CORRECTIONS 2. ALL 15 & 20 -- 120V RECEPTACLES -- INSTALLED IN COMMERICAL KITCHENS TO BE GFI PROTECTED 3. NEED NEW PANEL DIRECTORIES ALL PANELS 4. INSTALL APPROVED HANDLE TIES ON BREAKERS |