Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/20/2007 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 11/16/2007 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. HAVE OVERFILLED J-BOXES - NEC 314.16 2. MC TO BE SECURED WITHIN 12" OF J-BOXES/TERMINATIONS NEC 330.30 3. SUPPORT WIRES TO BE SECURED AT BOTH ENDS - NEC 300.11 4. REMOVE UNUSED RACEWAYS, SEAL UNUSED OPENINGS NEC 110.12A 5. SUPPORT WIRE (2) FOR EACH 4' TRACK 6. WATER HEATER NOT IN 7. SECURE FIXTURES TO GRID 8. CLOSE OPEN J-BOXES |
|
| 11/15/2007 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* FLOOR WET NO INSPECTION |