Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/20/2007 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 10/24/2007 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* INSPECTION FOR SERVICE ONLY 1. NEED TO POST BOND 2. NEED TO ADD TEMPORARY POWER FOR TEST TO PERMIT 3. IDENTIFY SERVICE DISCONNECT AS A "SERVICE DISCONNECT" 4. PANEL EQUIPMENT GROUNDING CONDUCTOR TO TERMINATE ON NEUTRAL BLOCK OF DISCONNECT, NOT USED AS A BONDING CONDUCTOR. 5. BOND METER BASE ENCLOSURE 6. INSTALL SERVICE CONDUCTORS LINE SIDE OF METER PARTIAL INSPECTION ONLY *POWER WILL NOT BE ENERGIZED WITH OPEN WIRING ON INTERIOR |
|
| 10/08/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. PROTECT CONDUIT ENDS FROM SHARP METAL EDGES FOR VDV CABLING 2. FINISH DEMO OK WALLS AFTER DEMO |