Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T07CM03132
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/23/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
04/14/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
01/30/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. SPLICES IN HARD HOLE ENCLOSURES TO BE LISTED FOR WET LOCATION - NEC 314.30 2. NEED 2 POLE BREAKERS FOR 208V CIRCUITS OR APPROVED HANDLE TIES 3. SOME CONTACTORS ARE REGISTERED COMPONENTS AND NOT LISTED - NEC 110.3 4. PROVIDE INSTRUCTIONS FOR CONTACTORS 5. NEED POWER ON TO GET FINAL 6. HAVE ELECTRICAL CONTRACTOR ONSIDE FOR NEXT INSPECTION |
|
01/23/2008 | ELECTRIC - FINAL | Not ready for Inspection |