Permit: T07CM03132


Addresses:

10332 E VALENCIA RD

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
06/23/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
04/14/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
01/30/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. SPLICES IN HARD HOLE ENCLOSURES TO BE LISTED FOR WET LOCATION - NEC 314.30
2. NEED 2 POLE BREAKERS FOR 208V CIRCUITS OR APPROVED HANDLE TIES
3. SOME CONTACTORS ARE REGISTERED COMPONENTS AND NOT LISTED - NEC 110.3
4. PROVIDE INSTRUCTIONS FOR CONTACTORS
5. NEED POWER ON TO GET FINAL
6. HAVE ELECTRICAL CONTRACTOR ONSIDE FOR NEXT INSPECTION
01/23/2008 ELECTRIC - FINAL Not ready for Inspection