Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/17/2008 | FIRE - FINAL | Approved | ||
| 01/14/2008 | FIRE - FINAL | Denied | 1.) Rehang insulation on 2nd floor, blocking sprinkler coverage. 2.) Repair exit sign rear exit door. 3.) Replace painted sprinkler heads by bathrooms (x5) need to check all heads for paint. 4.) Remove slide bolt lock from rear exit door w/panic hardware. 5.) Need up to date fire sprinkler inspection done, this is to be done yearly, Last inspevtion on file 02/14/2005. 6.) Need up to date fire alarm check vavle inspection this is to be done every 5 years nothing on file. 7.) Padlock PIV handle. |