Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/14/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 01/09/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : There is no access to the site.| 920* 1. CALLED, LEFT MESSAGE WHEN 30 MIN. OUT UNIT LOCKED NO ONE ON SITE 2. RECALL WHEN READY |
|
| 12/28/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* FINISH VDV CABLING |
|
| 11/21/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. PLEASE VERIFY AUTHENTICITY OF LABELING FOR ESPRESSO MACHINE 2. ATTACH FIXTURES TO GRID 410.16 3. SUPPORT VDV CABLING (#2 INSPECTION 10/30/07) 4. BOXES MORE THAN 1/8" AROUND BOX 314.21 5. LABEL TIME CLOCK TO WHAT IT OPERATES 6. DISCONNECTING MEANS NEEDED FOR WATER HEATER 7. WATER HEATER NOT ON PLANS NEED LOCATION & LOADS 8. LIGHT FIXTURES NOT AS PER PLANS 9. SUPPORT M/C CABLE ABOVE CEILING |