Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T07CM03118
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/14/2008 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
10/09/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK WALLS & COUNTER |
|
09/18/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. SUPPORT CONDUITS 3' OF BOXES 2. FILL UNUSED OPENINGS IN BOXES 3. TIGHTEN LOOSE FITTINGS OK WALLS AFTER CORRECTIONS *NOTE BOXES 314.20 |