Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/05/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 09/27/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. INVERTER DC TERMINAL LABELING CALL FOR #4 - 8 75 DEG COPPER WIRE ONLY - #10 IS INSTALLED 2. GROUNDING ELECTRODE CONDUCTOR (EXISTING) TO BE CONTINUOUS TO TERMINAL BAR 250.64 3. PLEASE OPEN METER TO INSPECT BONDING OF PV GROUNDING ELECTRODE CONDUCTOR PER 250.64 4. BOND HUB PER MANUFACTURES INSTRUCTIONS TO MEET REQUIREMENTS OF 250.64 5. PLEASE ADDRESS SERVICE WITH A PERMANENT METAL LABEL |
|
| 09/26/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* |