Inspection Status: Approved
Inspection History: EXCAVATION/LAYOUT REBAR & ZON
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/14/2008 | EXCAVATION/LAYOUT REBAR & ZON | Approved | IVRS - Inspection :* | |
| 03/19/2008 | EXCAVATION/LAYOUT REBAR & ZON | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) COMPLY WITH FOUNDATION PLAN DETAIL A/2 12" MIN. FOOTER DEPTH 19" MIN FOOTER WIDTH WITH #4 BARS 2) PORCH FOOTERS OK TO BURY 3) RECALL 1005 INSPECTION 4) EXPOSE ALL BRACED PANELS 5) RECALL 1025 INSPECTION |
|
| 03/05/2008 | EXCAVATION/LAYOUT REBAR & ZON | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NEED TO UNCOVER FOOTINGS AT CORNER OF HOUSE (BOTH CORNERS) TO VERIFY DEPTH OF FOOTERS AND AT SUPPORT POST 2) 2 X 4 DROPPED CEILING CALLS FOR 16" ON CENTER 3) WORK STARTED WITHOUT PERMITS-DID NOT WANT TO GO FURTHER INTO INSPECTIONS UNTIL FOOTERS HAVE BEEN APPROVED |