Permit: T07CM03066

Parcel: 141312880

Inspection Status: Approved

Inspection History: FRAMING

Permit Number - T07CM03066

Inspection Description - FRAMING

Inspection Status - Approved

Date Description Inspector Results Comments
10/18/2007 FRAMING Approved IVRS - Inspection :*
10/17/2007 FRAMING Partial Approval IVRS - Inspection :*
1) CONTINOUS SHEAR TRANSFER BLOCKING AT H20 HTR
2) USE A35'S AT TOP OF SHEAR WALL NOT H2.5 PUT ON OTHER SIDE OF WALL
3) BANG PLATES AT H20 SERV., AND AT RANGE AREA GARAGE SIDE
4) SCREW LAUNDRY BOX IN ALL THE WAY
10/12/2007 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) REAR BALCONY GUARD RAIL EAST END TO BE MIN. 36" HIGH
2) AT DRYER EXHAUST VENT (INTERIOR) CONNECTION BOX. STUD CUT AT TOP AND BOTTOM, INSTALL LET IN
3) GLUE LAM NOTCHED 1 1/2" AT GARAGE, BLOCK AT SIDE INSTALL A HANGER 4 X 10 TYPE
4) AT GARAGE FURNACE PLATFORM SHEETROCK TO BE CONTINOUS BLOCK OSB, FINISH A.35'S AT 24" ON CENTER TRUSS TO WALL
5) BANG PLATE (H20 SERVICE) LINES AT GARAGE