Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/18/2007 | FRAMING | Approved | IVRS - Inspection :* | |
| 10/17/2007 | FRAMING | Partial Approval | IVRS - Inspection :* 1) CONTINOUS SHEAR TRANSFER BLOCKING AT H20 HTR 2) USE A35'S AT TOP OF SHEAR WALL NOT H2.5 PUT ON OTHER SIDE OF WALL 3) BANG PLATES AT H20 SERV., AND AT RANGE AREA GARAGE SIDE 4) SCREW LAUNDRY BOX IN ALL THE WAY |
|
| 10/12/2007 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) REAR BALCONY GUARD RAIL EAST END TO BE MIN. 36" HIGH 2) AT DRYER EXHAUST VENT (INTERIOR) CONNECTION BOX. STUD CUT AT TOP AND BOTTOM, INSTALL LET IN 3) GLUE LAM NOTCHED 1 1/2" AT GARAGE, BLOCK AT SIDE INSTALL A HANGER 4 X 10 TYPE 4) AT GARAGE FURNACE PLATFORM SHEETROCK TO BE CONTINOUS BLOCK OSB, FINISH A.35'S AT 24" ON CENTER TRUSS TO WALL 5) BANG PLATE (H20 SERVICE) LINES AT GARAGE |