Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/03/2009 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 10/26/2009 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1. PROVIDE MIN 3" BEADED COLLARS @ FLEX CONNECTORS 2. VERIFY SOUND ATTENUATION DETAIL 8 M201 3. FLEX DUCT NOT TO EXCEED 8' IN LENGTH NOTES M101 4. PROVIDE PROPER TENSIONING TOOL FOR FLEX INSTALLATION 6. DUCT SMOKE DETECTORS NOT IN APPROVED LOCATION SEE INSTALLATION INSTRUCTIONS 7. PROVIDE FULL RADIUS OF FLEX DUCT 8. PROVIDE DAMPERS AT EXHAUST |