Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - UFER
Permit Number - T07CM03057
Inspection Description - ELECTRIC - UFER
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/20/2010 | ELECTRIC - UFER | Approved | IVRS - Inspection :* | |
01/13/2010 | ELECTRIC - UFER | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* ROOF: 1) LABEL DISCONNECTS 2) SUPPORT BOX ON RACEWAY 3) CHECK POLES NEXT TIME-PLEASE HAVE TOOL TO ACCESS 4) OUTDOOR RECEPT COVERS TO BE WEATHER PROOF WETHER OR NOT PLUGED INTO 408.6 5) BOXES MORE THAN 1/4" 314.20 6) LABEL PANEL COVERS 7) PROTECT CONDUCTOR AT FITTING 352.46 AND 300.4 8) CONDUCTORS TO BE COLORED PER 210.5 (C) OF AMENDMENTS 9) SUPPORT BOX AND CONDUITS BELOW PANEL AND CONTACTORS 10) ONLY ONE CONDUCTOR PER LUG 11) SHEET METAL THREAD SCREWS NOT ALLOWED FOR GROUNDING 250.8 12) CLEAN SURFACE UNDER GROUND LUG 250.12 13) MAINTAIN WORKING CLEARANCE OUTSIDE PANEL 110.26 14) RACEWAYS ENTERING SWITCH BOARD PER 408.5 |
|
08/10/2009 | ELECTRIC - UFER | Partial Approval | THIS ELECTRODE GROUNDING SYSTEM IS COMPLETE WITH THE EXCEPTION OF POSSIBLE GAS AND WATER BONDS. OK FOR TEMP SERVICE. | |
08/06/2009 | ELECTRIC - UFER | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) THIS INSTALLATION OF ELECTRICAL IS NOT SAFE BASED ON THE INFORMATION PROVIDED TO ME (THIS INSPECTOR) FOR WORKING CONDITIONS ACCORDING TO THE FOLLOWING CODES 110.2, 110.3 (A) (8), 110.27 (B), 240.24 (C), 590.2 (B) 2) NO HOUSE PANEL IS LOCATED WITHIN THE SWITCHBOARD TO BE ENERGIZED 3) NO FENCE OR BOLLARDS ARE INSTALLED-ONLY 'T' POST AND RIBBON |
|
07/29/2009 | ELECTRIC - UFER | Partial Approval | IVRS - Inspection :* | |
07/28/2009 | ELECTRIC - UFER | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) PICK COPPER UP OFF OF BOTTOM 2) BOND TO REBAR |
|
04/21/2009 | ELECTRIC - UFER | Not ready for Inspection | IVRS - Inspection :* | |
04/01/2009 | ELECTRIC - UFER | Partial Approval | IVRS - Inspection :* OK PVC CONDUITS POLE TO POLE -- TO SERVICE OK 9 POLE BASES OK 4" TEP TO BUILDING |