Inspection History: ELECTRIC - UFER

Permit Number - T07CM03057

Inspection Description - ELECTRIC - UFER

Inspection Status - Approved

Date Description Inspector Results Comments
01/20/2010 ELECTRIC - UFER Approved IVRS - Inspection :*
01/13/2010 ELECTRIC - UFER Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
ROOF:
1) LABEL DISCONNECTS
2) SUPPORT BOX ON RACEWAY
3) CHECK POLES NEXT TIME-PLEASE HAVE TOOL TO ACCESS
4) OUTDOOR RECEPT COVERS TO BE WEATHER PROOF WETHER OR NOT PLUGED INTO 408.6
5) BOXES MORE THAN 1/4" 314.20
6) LABEL PANEL COVERS
7) PROTECT CONDUCTOR AT FITTING 352.46 AND 300.4
8) CONDUCTORS TO BE COLORED PER 210.5 (C) OF AMENDMENTS
9) SUPPORT BOX AND CONDUITS BELOW PANEL AND CONTACTORS
10) ONLY ONE CONDUCTOR PER LUG
11) SHEET METAL THREAD SCREWS NOT ALLOWED FOR GROUNDING 250.8
12) CLEAN SURFACE UNDER GROUND LUG 250.12
13) MAINTAIN WORKING CLEARANCE OUTSIDE PANEL 110.26
14) RACEWAYS ENTERING SWITCH BOARD PER 408.5
08/10/2009 ELECTRIC - UFER Partial Approval THIS ELECTRODE GROUNDING SYSTEM IS COMPLETE WITH THE EXCEPTION OF POSSIBLE GAS AND WATER BONDS. OK FOR TEMP SERVICE.
08/06/2009 ELECTRIC - UFER Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) THIS INSTALLATION OF ELECTRICAL IS NOT SAFE BASED ON THE INFORMATION PROVIDED TO ME (THIS INSPECTOR) FOR WORKING CONDITIONS ACCORDING TO THE FOLLOWING CODES 110.2, 110.3 (A) (8), 110.27 (B), 240.24 (C), 590.2 (B)
2) NO HOUSE PANEL IS LOCATED WITHIN THE SWITCHBOARD TO BE ENERGIZED
3) NO FENCE OR BOLLARDS ARE INSTALLED-ONLY 'T' POST AND RIBBON
07/29/2009 ELECTRIC - UFER Partial Approval IVRS - Inspection :*
07/28/2009 ELECTRIC - UFER Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) PICK COPPER UP OFF OF BOTTOM
2) BOND TO REBAR
04/21/2009 ELECTRIC - UFER Not ready for Inspection IVRS - Inspection :*
04/01/2009 ELECTRIC - UFER Partial Approval IVRS - Inspection :*
OK PVC CONDUITS POLE TO POLE -- TO SERVICE
OK 9 POLE BASES
OK 4" TEP TO BUILDING