Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/27/2010 | FRAMING | Approved | IVRS - Inspection :* | |
| 01/05/2010 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) DUCT WORK IN GARAGE MUST BE 26 GAUGE METAL FOR FIRE SEPERATION 2) MISSING AB'S GARAGE PLATE JOINTS 3) MISSING GARAGE ATTIC ACCESS 4) FIRESTOP PENETRATIONS BASEMENT TO FIRST FLOOR 5) TERMINATE EXHAUST FAN MASTER BATH TO EXTERIOR 6) PROTECT DRYER VENT FHA STRAP TOP PLATE 7) BLOCK MECH PLENIUMS 8) STRAP BEAM GLUE LAMB KITCHEN 9) GROUND ALL METAL CEILING BOXES 10) BASEMENT KEY NOTE 4 ACCESS PANEL 11) COMPLY WITH STAIRWELL DETAIL 1/55 MISSING HARDWARE, TREADS AND FIREBLOCK 12) PROVIDE GAS BOND |
|
| 10/13/2009 | FRAMING | Not ready for Inspection | IVRS - Inspection :* 1) CANCELLED BY TONY, SPOKE TO HIM ON ITEMS OVER PHONE. WILL SUBMIT AS BUILTS |