Permit: T07CM03055

Parcel: 116240590


Addresses:

155 S PANORAMA CI

Inspection Status: Approved

Inspection History: ROOF NAILING

Date Description Inspector Results Comments
01/05/2010 ROOF NAILING Approved IVRS - Inspection :*
09/28/2009 ROOF NAILING Partial Approval IVRS - Inspection :*
1) NOTES 1-7 PREVIOUS
2) RECALL HAVE TONY MEET WITH INSPECTOR
09/16/2009 ROOF NAILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PAGE S/6 1ST FLOOR LEDGERS NOT INSTALLED PER PLAN. CALLS A.B3 ON PAGE S/3 FOR BOLTS 5/8 10" LONG AT 36" O.C., CAN'T BE SEEN - COVERED.
2. REAR PORCH COLUMNS NEED TO MEET WITH CONTRACTOR, CAN'T FIND DETAILS FOR BEAM COLS.
3. BEAM CONNECTIONS TO HOUSE NOT PER PLANS, PULIN STRAPS NOT INSTALLED PER PLAN
4. FOUND UNGROUTED CELL 1ST FLOOR BLOCK CRACKED
5. FROM LAST INSPECTION 3 1/8 X 12 BEAM AT STAIR IN BASEMENT NOT PER PLAN (SPAN)
6. REAR PORCH INTERMEDIATE COLUMN CONNECTINO NOT ON PLAN
7. NO DETAIL FOR TRUSS TO CMU AT WALL TO TRUSS PARALLEL SITUATION ONLY NOTED AS A.B.6 ON PAG S/3 NOT INSTALLED 1/2" BOLTS AT 48" O.C.
09/11/2009 ROOF NAILING Not ready for Inspection IVRS - Inspection :*
1) NEED COMPLETE SET OF TRUSS DRAWINGS, FOR FLOOR AND ROOF
2) EAST OF BASEMENT STAIR, BEAM AND FRAME NOT PER PLAN
3) QUEST ON PORCH COLUMNS CONNECTION AT FLOOR LEVEL 2/55 DOES NOT SHOW REBAR CONTINOUS
4) WALKED ROOF NAILING-OK
09/08/2009 ROOF NAILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NO ACCESS TO ROOF
2) NEED LADDER ON SITE