Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/16/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 08/14/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. SUPPORT WIRE TO BE ATTACHED AT BOTH ENDS - 300.11 2. ONLY ONE CONDUCTOR TO A LUG - 110.14 3. BOXES MORE THAN 1/4" FROM BOX TO SURFACE NEED AN APPROVED EXTENDER RING - 314.20 4. EXIT & EM TO BE ON CIRCUIT SERVED - 700.12 5. CLEAN EXCESS DIRT & FOREIGN MATERIAL FROM PANEL 6. MAIN BREAKER TO HAVE MANUFACTURES HOLDDOWN 408.16 7. CANNOT STACK LUGS PROVIDE SURFACE CONTACT |