Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/16/2007 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 08/14/2007 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
| 08/09/2007 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. SINGLE LINE DIAGRAM NOT CORRECT. PANEL AND TRANSFORMER WERE RELOCATED TO THIS AREA -- NOT "EXISTING" 2. HAVE BROKEN MC & PINCHED ALONG NEW WALL RECEPTACLES 3. WALLS, CEILING COVERED WITHOUT APPROVAL 4. SECURE FIXTURES TO GRID, SUPPORT WIRES TO CONNECT @ BOTH ENDS, SECURE FIXTURE TO J-BOX COVERS - NEC 300.11 5. HAVE OVERFILLED J-BOX - NEC 314.16 PARTIAL INSPECTION |
|
| 08/03/2007 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* REVISE PLANS TO SHOW ACTUAL (ALL) SCOPE OF WORK AND INCLUDE SINGLE LINE DIAGRAM OF ALTERED PANEL AND TRANSFORMER |