Permit: T07CM03033

Parcel: 117060940


Addresses:

45 N 5TH AV


Inspection Status: Approved

Inspection History: PLUMBING - PRE SLAB

Permit Number - T07CM03033

Inspection Description - PLUMBING - PRE SLAB

Inspection Status - Approved

Date Description Inspector Results Comments
09/16/2010 PLUMBING - PRE SLAB Approved IVRS - Inspection :*
01/14/2010 PLUMBING - PRE SLAB Partial Approval IVRS - Inspection :*
1) PERMIETER DRAIN OK
10/09/2009 PLUMBING - PRE SLAB Partial Approval IVRS - Inspection :*
1) FROM B TO F AND 2.1 TO 5 OK LEVEL 1
09/30/2009 PLUMBING - PRE SLAB Partial Approval IVRS - Inspection :*
1) REVIEWED I.P.C. REQUIREMENTS WITH DON, JOE AND BOB SHERRY
2) OK TO POUR
09/29/2009 PLUMBING - PRE SLAB Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PROVIDE PETITION OF APPEAL FOR IPC USE
2) 2-THREE INCH N/H RISERS FOR UPSTAIRS
3) 2-FOUR INCH CLEANOUT EXTENSIONS AT FLOOR SINK #1-TWO INCH IS NOT LARGE ENOUGH FOR C.W.V. BESIDES IT STILL NEEDS TO BE VENTED. 6" UNDER FLOOR IS SANITARY SEWER NOT CWV
09/21/2009 PLUMBING - PRE SLAB Partial Approval IVRS - Inspection :*
1) 6" ROOF DRAIN STUB UP ONLY IN SLAB AND OUT TEST OK
2) TRAP PRIMER OK TWO TYPE L COPPER
09/17/2009 PLUMBING - PRE SLAB Partial Approval IVRS - Inspection :*
6" DIP STUBBED THROUGH CONRETE POUT INTO GARAGE AND THEN THROUGH BUILDING
OK TO POUR S.T.O.F.
09/11/2009 PLUMBING - PRE SLAB Partial Approval 1) OK TO POUR CONCRETE
2) PIPE WRAPS OK
09/10/2009 PLUMBING - PRE SLAB Not ready for Inspection IVRS - Inspection :*
1) WRAP PIPE AND RECALL INSPECTION
07/23/2009 PLUMBING - PRE SLAB Partial Approval IVRS - Inspection :*
1) FLOOR DRAIN AND CLEANOUT ON FIRST FLOOR AT COLUMN B + 7.1 TEST OK
2) PRE-SLAB OK
07/22/2009 PLUMBING - PRE SLAB Not ready for Inspection IVRS - Inspection :*
07/17/2009 PLUMBING - PRE SLAB Partial Approval IVRS - Inspection :*
1) GRID LINE 1-6 AND A-F PRE SLAB ON B.1-OK
06/12/2009 PLUMBING - PRE SLAB Partial Approval IVRS - Inspection :*
GRID LINE 7 FROM A TO G
06/10/2009 PLUMBING - PRE SLAB Partial Approval IVRS - Inspection :*
DRAINS AND CLEANOUTS AND RISERS ALONG COLUMN B-4
OK TO COVER UNDERGROUND
05/12/2009 PLUMBING - PRE SLAB Partial Approval IVRS - Inspection :*
FLOOR DRAIN AND CLEANOUT UNDER STAIRWELL #3 TO OUTSIDE FOOTING, OK TO COVER
04/09/2009 PLUMBING - PRE SLAB Partial Approval IVRS - Inspection :*
03/25/2009 PLUMBING - PRE SLAB Partial Approval OK TO POUR CONCRETE
03/23/2009 PLUMBING - PRE SLAB Partial Approval IVRS - Inspection :*
COPPER DRAIN INSTALLED TO COLUMN H-8 AT
ELEVATOR PIT #5 & #6
OK TO COVER
03/19/2009 PLUMBING - PRE SLAB Partial Approval IVRS - Inspection :*
1 1/2 COPPER STUBBED UP FROM SUMP PIT OK TO COVER WITH CLEAN FILL
03/05/2009 PLUMBING - PRE SLAB Partial Approval IVRS - Inspection :*
6" WH DRAIN FROM STAIRWELL EAST TO CORNER AROUND CORNER TO PAST EXTERIOR WALL PLUS OR MINUS 6"
OK TO COVER
02/23/2009 PLUMBING - PRE SLAB Partial Approval IVRS - Inspection :*
1. PLEASE CALL IN THE CORRECT INSPECTION CODE
THIS INSPECTION IS FOR 03005
2. 3" N/H AREA DRAIN FROM UPPER C.O. THRU FLOOR SINK TO NEXT CLEANOUT AT STAIRWALL OK TO COVER
WATER TEST ONE RISER TO TEN FEET
03/10/2008 PLUMBING - PRE SLAB Partial Approval IVRS - Inspection :*
PRE-CONSTRUCTION MEETING WITH DON WILLIAMS