Permit: T07CM03033

Parcel: 117060940


Addresses:

45 N 5TH AV


Inspection Status: Approved

Inspection History: ELECTRIC - CONSTRUCTION POWER

Permit Number - T07CM03033

Inspection Description - ELECTRIC - CONSTRUCTION POWER

Inspection Status - Approved

Date Description Inspector Results Comments
09/29/2010 ELECTRIC - CONSTRUCTION POWER Approved
09/07/2010 ELECTRIC - CONSTRUCTION POWER Partial Approval Re: MLK Tower Electric Power Service Modification Inspection
1 N. 5th Ave.

The following is a description of what I witnessed.

On 9/3/2010, from approximately 2:40 pm to 3:00 pm the new electric power service to the address above was inspected. The new TEP transformer secondary terminations, the terminations at the buildings busbar, the new service feeder conductors and conduits were reviewed. Each conduit pull was balanced for phasing and the rotation & voltages were checked before the building was re-energized.

At approximately 3:00 pm the TEP Maproom was called and given approval for energization of 1 N. 5th Ave, TEP work order 192887, with ECO clearance. At 3:30 pm the TEP power was on and by 3:40 pm the subject buildings main switchgear was re-energized from the new service. After this the individual circuits of the building were re-energized as well. No incidents or disruptions of service were observed.

V. John Lundgren, PE
City of Tucson
General Services Dept.
Architecture and Engineering Division
John.Lundgren@tucsonaz.gov
Office: 520.837.6321
09/25/2009 ELECTRIC - CONSTRUCTION POWER Partial Approval IVRS - Inspection :*
1) TEMP SERVICE STRUCTURE AT NORTH END OF PROJECT
2) CALLED CLEARANCE INTO KATHY AT TEP 9/24/09-AM
12/15/2008 ELECTRIC - CONSTRUCTION POWER Partial Approval IVRS - Inspection :*
1) OK 3/4" AND 1" PVC FOR ELEVATORS AS MARKED
12/11/2008 ELECTRIC - CONSTRUCTION POWER Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. LABELING TO BE PERMANENT
2. FINISH PREVIOUS ITEMS
12/09/2008 ELECTRIC - CONSTRUCTION POWER Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. PLEASE HAVE ELECTRICIAN PRESENT
2. LABEL DISCONNECTS
3. INSTALL MAIN BONDING JUMPER
4. BRING NEUTRAL TO SERVICE DISCONNECT - 250.24(C)
5. MAINTAIN CLEARANCES FOR TRANSFORMER -- 450.9
6. SECURE TRANSFORMER TO PAD
7. LABEL BREAKERS PER 408.4
8. INSTALL GROUNDING ELECTRODE CONDUCTOR AND MAIN BONDING JUMPER SAME LUG (XFMR)
9. TIGHTEN LOOSE CONDUCTORS (XFMR)
10. INSTALL REJECTION PINS