Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - UNDERGROUND
Permit Number - T07CM03033
Inspection Description - ELECTRIC - UNDERGROUND
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/29/2010 | ELECTRIC - UNDERGROUND | Approved | ||
09/17/2010 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1) OK CONTINUE 4" PVC FOR FIBER OPTICS AND LIGHT POLE FEED AT LONGRESS STREET |
|
07/13/2010 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1) OK U.G. FOR FIBER OPTICS WEST OF BLDG |
|
05/21/2010 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1) OK X-FORMERS CONDUITS IN SLAB J-2 CAB, AREA |
|
04/01/2009 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* OK 1" AND 2" FROM NW ELEC. ROOM TO NW WALL FOR U.G. FIRE PUMP FEEDER |
|
01/12/2009 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* | |
12/15/2008 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* | |
07/03/2008 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* OK 3 - 4" PVC U.G FOR COX & QWEST TO SOUTH EAST CORNER OF EXISTING APARTMENT BUILDING. |
|
06/10/2008 | ELECTRIC - UNDERGROUND | Not ready for Inspection | IVRS - Inspection :* | |
06/02/2008 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* OK REMAINDER OF POLE LIGHTING TO PEDESTAL (WEST SIDE POLE LIGHTING 2 - 2" PVC) |
|
05/29/2008 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* OK TO COVER SERVICE RACEWAYS MACARTHUR CT CAN AND MLK BUILDING TEMP. TRANSFORMER TO BUILDING CALL FOR SERVICE INSPECTION WHEN READY INSTALL WARNING RIBBONS WHEN BACKFILL BONDING JUMPERS SIZED PER NEC TABLE 250.66 |
|
05/27/2008 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* OK TRENCH COVER WEST SIDE JOINT UTILITY PARTIAL RUN |
|
05/21/2008 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* OK PVC UNDERGROUND AS MARKED ON PAGE E1.03 IN OFFICE |
|
05/15/2008 | ELECTRIC - UNDERGROUND | Not ready for Inspection | IVRS - Inspection :* WORK IN PROGRESS MOUNTAIN POWER - PATRICK @ 955-0211 SUPERINTENDENT - DAN @ 471-8421 |
|
03/27/2008 | ELECTRIC - UNDERGROUND | Not ready for Inspection | IVRS - Inspection :* | |
03/20/2008 | ELECTRIC - UNDERGROUND | Not ready for Inspection | IVRS - Inspection :* | |
03/10/2008 | ELECTRIC - UNDERGROUND | Not ready for Inspection | IVRS - Inspection :* NO WORK AT THIS TIME |