Permit: T07CM03033

Parcel: 117060940


Addresses:

45 N 5TH AV


Inspection Status: Approved

Inspection History: STEM WALL/RETAINING WALL

Permit Number - T07CM03033

Inspection Description - STEM WALL/RETAINING WALL

Inspection Status - Approved

Date Description Inspector Results Comments
09/10/2009 STEM WALL/RETAINING WALL Approved IVRS - Inspection :*
09/09/2009 STEM WALL/RETAINING WALL Partial Approval IVRS - Inspection :*
09/08/2009 STEM WALL/RETAINING WALL Not ready for Inspection IVRS - Inspection :*
1) CANCELLED
08/17/2009 STEM WALL/RETAINING WALL Partial Approval IVRS - Inspection :*
1) COLS PLACED THIS AM OK
08/14/2009 STEM WALL/RETAINING WALL Partial Approval IVRS - Inspection :*
1) OK TO CLOSE REMAINING COLUMNS LEVEL B1 GRID LINES F,G,H
08/07/2009 STEM WALL/RETAINING WALL Partial Approval IVRS - Inspection :*
08/06/2009 STEM WALL/RETAINING WALL Partial Approval IVRS - Inspection :*
1) LEVEL B1 COLUMNS LINES G, H AND J TO LINE 9 EXCEPT G-7 (ELEVATION ISSUE)
07/30/2009 STEM WALL/RETAINING WALL Partial Approval IVRS - Inspection :*
PLACEMENT OK
07/29/2009 STEM WALL/RETAINING WALL Partial Approval REMAINING COLS LEVEL B1 AREA 1-6.5 OK TO PLACE
07/28/2009 STEM WALL/RETAINING WALL Partial Approval IVRS - Inspection :*
1) POURED BEFORE ARRIVAL PER SUPER SPECIAL INSPECTED
2) 6 COLUMNS E2, BCD #4, D#5 & 6
07/27/2009 STEM WALL/RETAINING WALL Partial Approval IVRS - Inspection :*
1) 5 COLUMNS CLEARANCE ON ELECTRIC CONDUIT-OK NORTH OF GRID LINE DON B1
07/23/2009 STEM WALL/RETAINING WALL Partial Approval IVRS - Inspection :*
1) COLUMN LEVEL B1 2/D,E,F; 3/B,E; 4/B,C,D,E; 5/B,D,E; 6/B,C,E-OK TO CLOSE
07/15/2009 STEM WALL/RETAINING WALL Partial Approval IVRS - Inspection :*
1) PROGRESS ON COLUMN PLACEMENTS-OK
07/14/2009 STEM WALL/RETAINING WALL Partial Approval 1) PROGRESS OK
07/13/2009 STEM WALL/RETAINING WALL Partial Approval IVRS - Inspection :*
1) OK TO CLOSE ALL COLS LEVEL B1 AT 1-6/N-F
07/09/2009 STEM WALL/RETAINING WALL Partial Approval IVRS - Inspection :*
1) PLACEMENT THIS AM OK-KEEP CONDUITS AWAY FROM VERT BAR
07/07/2009 STEM WALL/RETAINING WALL Partial Approval IVRS - Inspection :*
1) P-(1) C,D,E,F/8,9 OK TO CLOSE
2) J/2,3,4,6 LEVEL B1 OK TO CLOSE
3) K/3.1 LEVEL B1 OK TO CLOSE
07/06/2009 STEM WALL/RETAINING WALL Partial Approval IVRS - Inspection :*
1) D-E-F/8 & 9 CHECK ? VERT OUT OF TIE
06/03/2009 STEM WALL/RETAINING WALL Partial Approval IVRS - Inspection :*
1) SHOTCRETE COMPLETE (LESS SOME SKIM CONT)
06/02/2009 STEM WALL/RETAINING WALL Partial Approval IVRS - Inspection :*
PROGRESS ON LINE A - SHOTCRETE OK
06/01/2009 STEM WALL/RETAINING WALL Partial Approval IVRS - Inspection :*
1. SHOTCRETE WALL LINE 1 DONE; PROGRESS LINE A OK
2. LINE 4 COLS. DONE OK
05/28/2009 STEM WALL/RETAINING WALL Partial Approval IVRS - Inspection :*
1. SHOTCRETE PLACEMENT LINE 1 TO GRID B OK LOWER LEVEL LINE 1 TO GRID E ON 2ND LEVEL
2. COLUMNS PLACED OK YESTERDAY; CLOSING LINE 4 TODAY
OK TO PLACE
05/26/2009 STEM WALL/RETAINING WALL Partial Approval IVRS - Inspection :*
1. FORMS SET LINES 3, 5, 6 AND @ 4/F
2. CORRECTIONS MADE LINE A - OK TO COVER
3. 3 PANELS (LOWER LEVEL) LINE 1 HAD SHOTCRETE PLACED TODAY OK
05/22/2009 STEM WALL/RETAINING WALL Partial Approval IVRS - Inspection :*
EXTERIOR WALL STEEL LINE A SUBSTANTIALLY COMPLETE
OK TO BEGIN SHOTCRETE WHEN SPEC. INSP. CONFIRMS MINOR CORRECTIONS.
05/21/2009 STEM WALL/RETAINING WALL Not ready for Inspection IVRS - Inspection :*
05/20/2009 STEM WALL/RETAINING WALL Partial Approval 1) LINE 1 OK FOR SHOTCRETE WHEN SPECIAL INSP CONFIRMS FINAL PLACEMENT OF CORNER BARS AT 1/A.
2) REMAINING COLS UP TO GRIDLINE 6 OK TO CLOSE UP; COLS 3B, 5B & 4E REQUIRE SOME ADJUSTMENT AT THE BOTTOM WHICH SPECIAL INSPECTOR MAY CONFIRM.
05/18/2009 STEM WALL/RETAINING WALL Partial Approval IVRS - Inspection :*
WATER PROOFING GENERALLY OK
SOME AREAS ALONG BOTTOM TO BE PUSHED BACK
05/15/2009 STEM WALL/RETAINING WALL Cancelled IVRS - RI canceled
05/13/2009 STEM WALL/RETAINING WALL Partial Approval IVRS - Inspection :*
1) STAIR STEM
05/08/2009 STEM WALL/RETAINING WALL Partial Approval 1) FOOTING FOR STAIR @ C-E/5-6 AREA OK
2) COLUMN STEEL FOR REMAINING COLUMNS B-F/3-6 OK BUT I STILL NEED TO SEE FINAL LAYOUTS BEFORE CLOSING
05/05/2009 STEM WALL/RETAINING WALL Partial Approval IVRS - Inspection :*
GRID LINE 3/B
4/B, C, D -- OK TO CLOSE
04/29/2009 STEM WALL/RETAINING WALL Partial Approval IVRS - Inspection :*
04/28/2009 STEM WALL/RETAINING WALL Partial Approval IVRS - Inspection :*
CLOSE UP OF COLS. @ 2/B, C, D, E AND 3/B, F OK
OK TO PLACE
04/27/2009 STEM WALL/RETAINING WALL Partial Approval IVRS - Inspection :*
GRID LINE 2/B,C,D,E AND 3/D AND F
COL. STEEL OK; OK TO CLOSE
03/25/2009 STEM WALL/RETAINING WALL Partial Approval IVRS - Inspection :*
CONTINUATION OK SOIL NAIL WALL OK
03/19/2009 STEM WALL/RETAINING WALL Partial Approval IVRS - Inspection :*
1. OK TO PLACE CONCRETE IN COL @ E/7.1
2. PROGRESS ON SOIL NAILS OK
03/18/2009 STEM WALL/RETAINING WALL Partial Approval IVRS - Inspection :*
MASONRY STEMS @ 1/N AND 10/M AREAS
03/16/2009 STEM WALL/RETAINING WALL Partial Approval IVRS - Inspection :*
1. COL. E/7.1 OK TO CLOSE AND PLACE
2. PLACEMENT @ 7.1/D, 7/D, E, F AND J/9 OK
3. SHOTCRETE AND FINISH OK TO 1/G OK
03/12/2009 STEM WALL/RETAINING WALL Partial Approval IVRS - Inspection :*
1. HOOKS ON COL. @ E/7.1 MUST ENCAGE LOWER DOWELS
2. CLEARANCE @ F/7D IS NOT SUFFICIENT @ BOTTOM
3. PROGRESS ON SOIL LINE A OK
4. PROGRESS ON SHOTCRETE LINE A OK
5. OK TO PLACE CONCRETE FOR C.I.P LINE K/LINE 9
6. OK TO CLOSE COLUMNS LINE 7/D, E, F AND J/9
03/11/2009 STEM WALL/RETAINING WALL Partial Approval IVRS - Inspection :*
1. OK TO CLOSE C.I.P WALL @ K AND 9
2. OK TO CLOSE COLUMN @ J/9
3. SHOTCRETE APPLICATION PROGRESS LINE 1 AND N
LOWER TIER OK
03/10/2009 STEM WALL/RETAINING WALL Partial Approval IVRS - Inspection :*
1. OK TO CLOSE UP WALLS @ SE CORNER (LINE K; LINE 9)
WHEN SPECIAL INSP. GIVES OK
2. FINISH CONT TO 3/N OK
03/09/2009 STEM WALL/RETAINING WALL Partial Approval IVRS - Inspection :*
1. SHOTCRETE OK TOP TIER TO N/2
2. STEEL OK FOR SHOTCRETE PLACEMENT TO 1/G BOTH TIERS
03/06/2009 STEM WALL/RETAINING WALL Partial Approval IVRS - Inspection :*
1. NEW SHOTCRETE - LOWER TIER TO N/2 OK; UPPER TIER TO NS OK
2. STEEL IN OUTSIDE WALL LINE 1 TO 6 OK
RECALL WHEN WIRE IN
03/05/2009 STEM WALL/RETAINING WALL Partial Approval IVRS - Inspection :*
SHOTCRETE TO N/S UPPER TIER OK
03/04/2009 STEM WALL/RETAINING WALL Partial Approval IVRS - Inspection :*
PROGRESS WITH SHOTCRETE LINE N LOWER TIER TO LINE 3
03/03/2009 STEM WALL/RETAINING WALL Partial Approval 1) LINE N TO LINE 2 OK TO PLACE SHOTCRETE TOP AND BOTTOM TIERS.
2) TODAY'S PLACEMENT LOWER TIER TO LINE 6 OK.
02/27/2009 STEM WALL/RETAINING WALL Partial Approval IVRS - Inspection :*
1. 2ND TIER (TO RAMP) SHOTCRETE PLACED TO N/7 OK
2. OK TO PLACE SHOTCRETE TO N5 OK
02/26/2009 STEM WALL/RETAINING WALL Partial Approval IVRS - Inspection :*
1. SHOTCRETE PLACED TO M9 @ TOP TIER OK
2. OK TO PLACE SHOTCRETE LOWER TIER TO M/5
02/25/2009 STEM WALL/RETAINING WALL Partial Approval IVRS - Inspection :*
ALL PROGRESS OK
02/24/2009 STEM WALL/RETAINING WALL Partial Approval IVRS - Inspection :*
1. SHOTCRETE OK TO PLACE THROUGH PANEL 20 (M/7)
2. PLACEMENT OF SHOTCRETE TOP TIER THROUGH
PANEL AREA 13 OK
02/20/2009 STEM WALL/RETAINING WALL Partial Approval 1. TOP TIER SHOTCRETE TO LINE 6 ON 10
2. EXTERIOR WALL STEEL OK TO 1/G
02/19/2009 STEM WALL/RETAINING WALL Partial Approval IVRS - Inspection :*
PROGRESS SHOTCRETE TO 10/H.5
1ST TIER OK
02/18/2009 STEM WALL/RETAINING WALL Partial Approval IVRS - Inspection :*
SHOTCRETE 80 10 D
02/17/2009 STEM WALL/RETAINING WALL Partial Approval IVRS - Inspection :*
1. 2ND TIER LINE K/6-7.1 OK TO PLACE
2. SHOTCRETE TOP 1/2 LINE A IN PROGRESS
3. VERTICAL STEEL ALL OF LINE 10 OK TO COVER
02/13/2009 STEM WALL/RETAINING WALL Partial Approval IVRS - Inspection :*
1. EXTERIOR WALL UP TO 10/H OK TO SHEETROCK
2. 2ND TIER LINE K/6-8 OK TO CLOSE
3. SHOTCRETE OK LOWER TIER TO LINE L/8.2
02/12/2009 STEM WALL/RETAINING WALL Partial Approval IVRS - Inspection :*
1) REGAN LINE A; INSP ON SITE; 7 YARD BATCHES;
NOZZLEMAN OK APPLICATION METHOD OK
02/11/2009 STEM WALL/RETAINING WALL Partial Approval IVRS - Inspection :*
02/10/2009 STEM WALL/RETAINING WALL Partial Approval IVRS - Inspection :*
2ND TIER PANEL LINE K/4-6 OK TO PLACE
02/09/2009 STEM WALL/RETAINING WALL Partial Approval
02/05/2009 STEM WALL/RETAINING WALL Partial Approval IVRS - Inspection :*
OK TO PLACE LINE K/6-8
AND SUMP PIT @ 9/L
02/04/2009 STEM WALL/RETAINING WALL Partial Approval IVRS - Inspection :*
CIP WALL LINE K/6-8
OK TO CLOSE
02/02/2009 STEM WALL/RETAINING WALL Partial Approval IVRS - Inspection :*
COLS. & WALL NOTED 1/29 CLOSED & READY TO POUR
01/29/2009 STEM WALL/RETAINING WALL Partial Approval IVRS - Inspection :*
1. G&H/8; 7/H STEEL OK
OK TO CLOSE COL 5
2. CLIP WALL 4-6/LINE K OK TO CLOSE
3. READY TO START SHOTCRETE 6A - 1ST CORNER IN DOG LEG
01/26/2009 STEM WALL/RETAINING WALL Partial Approval IVRS - Inspection :*
CCS @ B/6 & C/6
01/21/2009 STEM WALL/RETAINING WALL Partial Approval IVRS - Inspection :*
GARAGE LEVEL - F, G, H/5 CC5 COLS.
01/16/2009 STEM WALL/RETAINING WALL Partial Approval IVRS - Inspection :*
4 EACH CCS COLS. @ G & H/9 & 6 GARAGE LEVEL
01/14/2009 STEM WALL/RETAINING WALL Partial Approval IVRS - Inspection :*
GARAGE LEVEL
1. CES # J & H/2; J, H, G/3; K/3.5 G,H, J/4.0
2. LINE J/7,8 OK WHEN SP. INSP. CONFIRMS
01/12/2009 STEM WALL/RETAINING WALL Partial Approval IVRS - Inspection :*
ELEVATOR PIT OK
01/07/2009 STEM WALL/RETAINING WALL Partial Approval IVRS - Inspection :*
OK TO PLACE ELEVATOR STEMS K-H/4.7-5.5
COL @ H/5
12/19/2008 STEM WALL/RETAINING WALL Cancelled IVRS - RI canceled
12/18/2008 STEM WALL/RETAINING WALL Partial Approval IVRS - Inspection :*
1. CCS CDS LEVEL B-2 @ LINE 2/F,G,H,J; LINE 3/G,H,J
LINE 3.5/K; LINE 4/G,H,J; LINE 10/J OK TO CLOSE
2. ENSURE 3 RINGS @ TOP ARE LEVEL @ VARIOUS LOCATIONS
12/16/2008 STEM WALL/RETAINING WALL Partial Approval IVRS - Inspection :*
OK TO CLOSE STEMS AND COLS. IN ELEVATOR PITS
12/15/2008 STEM WALL/RETAINING WALL Cancelled IVRS - RI canceled
11/18/2008 STEM WALL/RETAINING WALL Partial Approval IVRS - Inspection :*
11/13/2008 STEM WALL/RETAINING WALL Partial Approval IVRS - Inspection :*
E/8 SPECIAL INSPECTIONS REVIEWED THROUGH 11/12/08
10/22/2008 STEM WALL/RETAINING WALL Partial Approval IVRS - Inspection :*
10/10/2008 STEM WALL/RETAINING WALL Partial Approval IVRS - Inspection :*
ALL SPECIAL INSPECTION THROUGH
TODAY REVIEWED & ACCEPTED
10/03/2008 STEM WALL/RETAINING WALL Partial Approval IVRS - Inspection :*
SPECIAL INSP. REPORTS FOR SOIL NAIL RETENTION WALL
REVIEWED AND ACCEPTED THROUGH 10/3/08
09/25/2008 STEM WALL/RETAINING WALL Partial Approval IVRS - Inspection :*
SOIL NAIL AND RETENTION WALL
REPORTS REVIEWED AND ACCEPTED
THROUGH 9/24/08
09/19/2008 STEM WALL/RETAINING WALL Partial Approval IVRS - Inspection :*
SOIL NAIL/RETENTION WALL SPECIAL INSP. REPORTS REVIEWED AND ACCEPTED THRU 9/19/08
09/12/2008 STEM WALL/RETAINING WALL Partial Approval IVRS - Inspection :*
SOIL NAILS AND SHOTCRETE REPORTS REVIEWED AND ACCEPTED THROUGH 9/11/08

E.O.R NEEDS TO PUT IN WRITING THAT 24 DEG - 28 DEG DRILLING ANGLE OK ON BOTTOM ROW

RFI OK OR EMAIL
NO SEAL REQUIRED
09/05/2008 STEM WALL/RETAINING WALL Partial Approval IVRS - Inspection :*
REVIEWED SP. INSP. REPORTS FOR SOIL WALL/SHOTCRETE
REPORTS THROUGH 9/4/08 COMPLETE
08/29/2008 STEM WALL/RETAINING WALL Partial Approval IVRS - Inspection :*
REVIEWED SPECIAL INSP. REPORTS OF
SOIL WALL/SHOTCRETE
WALLS UP TO 8/28/08
ALL PROGRESS OK