Permit: T07CM03032

Parcel: 108240910


Addresses:

2478 E RIVER RD

Inspection Status: Approved

Inspection History: ELECTRIC - CABLE DROP

Date Description Inspector Results Comments
04/08/2008 ELECTRIC - CABLE DROP Approved IVRS - Inspection :*
03/27/2008 ELECTRIC - CABLE DROP Denied IVRS - Inspection :
See detailed listing on site.| 999*
03/17/2008 ELECTRIC - CABLE DROP Denied IVRS - Inspection :
The service is not per code.| 210*
1. NEED TO POST POWER BOND WITH C.O.T
2. INSTALL TEMP POWER GFI'S UNDER SERVICE DISCONNECT NOT INSIDE
3. IDENTIFY "SERVICE DISCONNECT" - NEC 230.72(B)
4. TIGHTEN ALL CONNECTIONS
5. G.E.C TO BOND TO SERVICE DISCONNECT ENCLOSURE NOT METER BASE - 250
6. BOND METAL WATER/SPRINKLER TO DISCONNECT ENCLOSURE - 250
7. ARRANGE BONDING CONDUCTORS TO PREVENT OBJECTIONABLE CURRENT - 250.6
8. 2 CONDUCTORS NOT UNDER SAME LUG - NEC 110.3(B)
9. REMOVE UNUSED RACEWAY BETWEEN ENCLOSURES
10. STRAP EMT