Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T07CM03032
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/08/2008 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
03/27/2008 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PANEL NOT TO BE IN CLOSET, TO HAVE PROPER FRONT WORKING CLEARANCE 2. INSTALL NAIL PLATES AS NEEDED 3. IDENTIFY WHITE USED AS HOT 4. PIGTAIL 3 WIRE NEUTRAL 5. GROUNDS & NEUTRALS TO BE SEPARATED IN SUB-PANEL 6. ROMEX TO HAVE CONNECTOR INTO PANEL AND EQUIPMENT |