Permit: T07CM03032

Parcel: 108240910


Addresses:

2478 E RIVER RD

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
04/08/2008 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
03/27/2008 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PANEL NOT TO BE IN CLOSET, TO HAVE PROPER FRONT WORKING CLEARANCE
2. INSTALL NAIL PLATES AS NEEDED
3. IDENTIFY WHITE USED AS HOT
4. PIGTAIL 3 WIRE NEUTRAL
5. GROUNDS & NEUTRALS TO BE SEPARATED IN SUB-PANEL
6. ROMEX TO HAVE CONNECTOR INTO PANEL AND EQUIPMENT