Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T07CM03030
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/18/2009 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
10/13/2008 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. FILL UNUSED OPENING IN WATER HEATER DISCONNECT 2. FINISH #4 & #5 |
|
10/09/2008 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) MAINTAIN WORKING CLEARANCES A/C DISCONNECT 110.26 2) TIGHTEN LOOSE FITTINGS 3) PVC ABOVE GRADE TO BE SCHEDULE 80 4) BOXES MORE THAN 1/4" + 1/8" 314.20 AND 314.21 ALSO COMBUSTIBLES 5) EXIT AND EM LIGHTS TO BE PER 700.12 6) CLEAN EXCESS DIRT AND FOREIGN MATERIAL FROM FLOOR BOXES 110.12 7) MAINTAIN WORKING CLEARANCE WATER HEATER DISCONNECT |
|
08/21/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
07/29/2008 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* WRONG BUILDING |
|
07/21/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK PANEL WALL 1. FINISH STRAIGHTENING & SUPPORTING CONDUIT RUNS |
|
07/16/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. SUPPORT CONDUIT WITH OTHER THAN PLUMBER TAPE 2. BOXES TO BE FLUSH IN COMBUSTIBLES 3. NO MORE THAN 360 DEG. IN CONDUIT RUNS OK TO DRYWALL AFTER CORRECTIONS AS DISCUSSED |
|
07/15/2008 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. MOVE M/C OUT OF CHANNELS TO PROTECT 2. SUPPORT 1" DATA CONDUITS AS PER CODES 3. PROTECT FLEX CONDUIT N-STUD CHANNELS 4. NO MORE THAN 360 DEG. IN CONDUIT RUNS 5. SUPPORT VDV CABLING IN WALLS 725.24, 800.24 6. SUPPORT TO BE EFFECTIVE 7. GROUND METAL JUNCTION BOXES 8. SEAL UNUSED CONDUIT OPENINGS 9. SUPPORT CONDUITS ABOVE PANELS 10. PROTECT PVC AT BASE PLATES |
|
07/11/2008 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : Work is not complete enough to inspect.| 950* 1. FINISH ELECTRICAL WORK 2. DO NOT DRYWALL |
|
07/10/2008 | ELECTRIC - INTERMEDIATE | Cancelled | IVRS - RI canceled | |
04/17/2008 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* OK FABRIC FOR CEILING |