Permit: T07CM03030

Parcel: 11520005D


Addresses:

1953 W GRANT RD 01


Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T07CM03030

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
06/18/2009 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
10/13/2008 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. FILL UNUSED OPENING IN WATER HEATER DISCONNECT
2. FINISH #4 & #5
10/09/2008 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) MAINTAIN WORKING CLEARANCES A/C DISCONNECT 110.26
2) TIGHTEN LOOSE FITTINGS
3) PVC ABOVE GRADE TO BE SCHEDULE 80
4) BOXES MORE THAN 1/4" + 1/8" 314.20 AND 314.21 ALSO COMBUSTIBLES
5) EXIT AND EM LIGHTS TO BE PER 700.12
6) CLEAN EXCESS DIRT AND FOREIGN MATERIAL FROM FLOOR BOXES 110.12
7) MAINTAIN WORKING CLEARANCE WATER HEATER DISCONNECT
08/21/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
07/29/2008 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
WRONG BUILDING
07/21/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK PANEL WALL

1. FINISH STRAIGHTENING & SUPPORTING CONDUIT RUNS
07/16/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. SUPPORT CONDUIT WITH OTHER THAN PLUMBER TAPE
2. BOXES TO BE FLUSH IN COMBUSTIBLES
3. NO MORE THAN 360 DEG. IN CONDUIT RUNS

OK TO DRYWALL AFTER CORRECTIONS AS DISCUSSED
07/15/2008 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. MOVE M/C OUT OF CHANNELS TO PROTECT
2. SUPPORT 1" DATA CONDUITS AS PER CODES
3. PROTECT FLEX CONDUIT N-STUD CHANNELS
4. NO MORE THAN 360 DEG. IN CONDUIT RUNS
5. SUPPORT VDV CABLING IN WALLS 725.24, 800.24
6. SUPPORT TO BE EFFECTIVE
7. GROUND METAL JUNCTION BOXES
8. SEAL UNUSED CONDUIT OPENINGS
9. SUPPORT CONDUITS ABOVE PANELS
10. PROTECT PVC AT BASE PLATES
07/11/2008 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
Work is not complete enough to inspect.| 950*
1. FINISH ELECTRICAL WORK
2. DO NOT DRYWALL
07/10/2008 ELECTRIC - INTERMEDIATE Cancelled IVRS - RI canceled
04/17/2008 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
OK FABRIC FOR CEILING