Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T07CM03029
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/17/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
10/13/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* FINISH #5 & #10 FROM 9/30/08 INSPECTION |
|
10/09/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
09/30/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. RECEPTACLE COVERS TO BE WEATHERPROOF WHETHER OR NOT PLUGGED INTO 406.8 2. LOOSE FITTING 3. SUPPORT CONDUITS ABOVE PANEL ALSO, USE APPROVED STAMPS 4. PANEL SCHEDULE TO BE LEGIBLE AS PER 408.4 5. BOXES MORE THAN 1/4" BOX TO SURFACE - 314.20 6. EXIT AND EM LIGHTS NOT WORKING 7. PLEASE PROVIDE LADDER OR ACCESS TO HIGH BAY LIGHTING 8. LABEL DISCONNECTS 9. USE APPROVED FITTINGS WITH CARFLEX 10. WIRING TO PUMPS NOT TO CODE |