Permit: T07CM03027

Parcel: 13329001A


Addresses:

545 N CAMINO SECO

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
05/16/2008 PLUMBING - FINAL Approved IVRS - Inspection :*
05/14/2008 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
- CORRECT LEAKS ON SINKS AND WC
- PROVIDE A CLEAN BACTERIA REPORT SEE SPEC. 3.04
- PROVIDE APPROVAL OF FIXTURE SPECIFICATION CHANGES
- REMOVE GALVANIZED FITTINGS AT FIXTURE CONNECTIONS
SEE SPEC. 2.04A FOR APPROVED MATERIAL TYPES
- REMOVE EXCESS FLUX AT SOLDIER JOINTS
(HAMMER ARRESTOR)
- CORRECT SPLASHING AT FS
- INSTALL DRAINAGE FITTINGS ON VENT BELOW FLOOD
LEVEL OF 3-COMP SINK
- ONLY ONE P-TRAP ALLOWED ON TRAP ARM, P-TRAP SHALL BE THE SAME SIZE AS TRAP ARM