Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T07CM03027
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/14/2008 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 04/18/2008 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* - LEVEL TRAP PRIMER DIST. CUP - PROVIDE SOV AT TRAP PRIMERS - SECURE MECHANICAL CLOSET FLANGES OR PROVIDE LISTING OF NOT REQUIRED - ABV CEILING VENTS NOT YET INSTALLED - KEEP OPEN PIPES PLUGGED, NOT TAPED DURING CONST. - ABV CEILING COOLER PIPING OK - PROVIDE SOV'S PER DETAIL 2, P-3 |
|
| 03/04/2008 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* PIPE INSULATION IN WALLS OK |
|
| 03/03/2008 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* CANCELED |
|
| 02/27/2008 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* DWV W/TEST TO CEILING HT OK NEED TO SEE PIPE INSULATION FOR APPROVAL TO COVER PIPE CHASES |
|
| 02/26/2008 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK TO INSULATE HW & CW EXTEND CO W/WYE PATTERN FITTINGS TEST |