Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T07CM03027
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/16/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 05/14/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. MAINTAIN CLEARANCE AT WATER HEATER DISCONNECT 2. PANEL LABELING TO BE AS PER 408.4 -- NO ABBREVIATIONS 3. NEED LABEL PER NOTE 11 OF PLANS 4. WEATHERPROOF COVER FOR RECEPTACLE TO BE AS PER 406.8 WHETHER OR NOT PLUGGED INTO 5. WHERE ARE DRINKING FOUNTAIN RECEPTACLES? 6. BOXES MORE THAN 1/4" IN NON-COMBUSTIBLE - 314.20 |
|
| 05/02/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* OK TEMP POWER FOR TEST SUBJECT TO BOND |