Inspection History Details
Inspection Status: Approved
Inspection History: REINFORCED MASONRY PRE-GROUT
Permit Number - T07CM03026
Inspection Description - REINFORCED MASONRY PRE-GROUT
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/14/2008 | REINFORCED MASONRY PRE-GROUT | Approved | IVRS - Inspection :* TOP OUT AT ALL MASONRY AT RESTROOMS/CONCESSIONS |
|
04/11/2008 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* INTERIOR SCREEN WALLS @ RESTROOM 1ST LIFT TO 5FT OK AND WOMENS PLUMBING CHASE TOPPED OUT |
|
04/09/2008 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* 1. NORTH WALL OF MENS ROOM PLUMBING CHASE TO 8'8" 2. SOUTH WALL MENS ROOM WEST HALF TO 9'8" EAST HALF TOP OUT 3. WOMENS ROOM TOP OUT @ BOTH CHASES - OK TO GROUT |
|
04/07/2008 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* 1. CMU @ BOTH PLUMBING CHASE WALLS @ WOMENS RESTROOM TO 8'8" 2. SOUTH WALL MENS ROOM CHASE TO 8'8" & NORTH WALL TO 6' - JANITORS ROOM TOP OUT, EXTERIOR CHASE TOPOUT AND DRINKING FOUNTAIN WALL TOP OUT |
|
04/03/2008 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* ALL FOUR INTERIOR PLUMBING WALLS FROM 0' TO 4' |
|
03/31/2008 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* MEN'S ROOM PLUMBING WALL FROM 0' TO 4' INTERIOR, RESTROOM WALLS, TOP OUT AND JANITORS ROOM FROM 4' TO 8' - OUTSIDE CHASE TO 4' AFFE |
|
03/27/2008 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* CONCESSIONS ROOM TOPOUT & 2 INTERIOR CMU RESTROOM WALL 3RD LIFT FROM 8' TO 12' |
|
03/24/2008 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* INTERIOR CMU WALLS FROM 4' TO 8' 2ND LIFT AND CONCESSION AREA TO 10' -- OK TO GROUT |
|
03/19/2008 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* 1. MAIN BLDG. TOP OUT @ 13' 2. CONCESSIONS AREA TO 7'4" W/CLEANOUTS |
|
03/13/2008 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* TOP OUT @ MAIN BLDG. PERIMETER WALLS ONLY |
|
03/06/2008 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* MAIN BUILDING EXTERIOR CMU WALLS FROM 4' TO 8' |
|
02/29/2008 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* CMU REINFORCMENT STEEL @ MAIN BUILDING EXCEPT JANITOR RM (4 SIDES) AND OPENING AT MECH. ROOM FROM 0' TO 4' AFF |
|
11/27/2007 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* 1) STEM WALL COMPLETE-OK TO GROUT |